Room Data
Room Temp: | 35° F with 90% RH |
Dimensions: | 7'-10" X 7'-10" X 7'-6". |
Doors: | 1 standard door(s). |
Ambient Temp.: | 85° F DB |
Ceiling Insulation: | 4" Extruded Polystyrene |
Ceiling K Factor: | 0.16 |
Ceiling Temperature: | 105° F |
Wall Insulation: | 4" Extruded Polystyrene |
Wall K Factor: | 0.16 |
Wall Temperature: | 85° F |
Floor Insulation: | 4" Extruded Polystyrene |
Floor K Factor: | 0.16 |
Floor Temperature: | 55° F |
Infiltration Data
Air Flow: | Based on 1.5 ASHRAE averages. |
Infil. Temp.: | 85° F DB (60% RH) infiltrating air. |
Product Data
Description: | Misc |
Max. Load: | 920 lbs./8 hrs. |
Enter Temp.: | 55° F |
Spec. Heats: | 0.9 above freeze/0.45 below freeze. |
Lat. Ht. Fusion: | 100 |
Packaging: | Varies |
Pulldown in: | 24 hrs. |
Final Temp.: | 35° F |
Freeze: | 27° F |
Respiration: | 0 lbs. (0 BTU/LB/Day) |
Miscellaneous Data
Personnel: | 0.0 person(s). |
Lighting: | 1 watt(s) per square foot. |
Motors: | 0.0 equiv. horsepower. |
Calculation Results
Wall Heat Gains: | 16582 | BTU/day (23.2% of total load). | Air Change: | 33278 | BTU/day (46.6% of total load). | Product Load: | 16568 | BTU/day (23.2% of total load). | Misc Load: | 5032 | BTU/day (7% of total load). | Daily Total: | 78605 | BTU/day.* | Cap. Required: | 4913 | BTUH at 16 hours per day runtime. |
* - Includes compensation for unforeseen high load conditions, excessive temperatures, unexpected increases in business, or product packaging.
All refrigeration sizes are estimates and may not accurately represent specific applications. In no event, shall U.S. Cooler be liable for special